Telephone : 056 650 660 | E-mail: info@limotec.be
MD780 gas & CO detection control panel
MD780 gas & CO detection control panel
MD780 gas & CO detection control panel

MD780 gas & CO detection control panel

The MD780 gas & CO detection control panel is appropriate to connect up to 8 external gas and/or CO detectors and operates in combination with the MD780 gas detector and the MD780 CO detector. The detected gas mixture is determined by the connected type of gas or CO detector.

The MD780 control panel is mounted in a plastic housing.The housing contains the console for operating the system, the power supply and provides the necessary space for the installation of two 12V 2.3Ah backup batteries.

The MD780 control panel is equipped with 3 adjustable alarm thresholds for gas detection and 4 adjustable alarm thresholds for CO detection. The alarm thresholds can be set individually for each zone.

The MD780 control panel is operated by means of the LCD with Touch screen. Each status of the control panel, such as "Alarm", "Fault" and "Disabled", is displayed via the LCD with Touch screen and by means of LED signalling.

The MD780 control panel has two access levels, the second level is password protected.

The logbook of the MD780 control panel can be consulted via the LCD with Touch screen and contains the last 500 messages and actions carried out.

The MD780 control panel is equipped with 6 freely programmable relay outputs, 2 freely programmable transistor outputs and 1 solid state relay. The MD780 control panel also has 2 external inputs assigned to the "Silence" and "Reset" functions.

With the help of the MD780 licensed configuration software, the MD780 control panel can be custom configured. The various system parameters, including the alarm thresholds per detector, the number and type of connected detectors, the assignment of the outputs to the various alarm and fault messages and the number of additonal relay cards, can be adapted.

Technical details

Description MD780 gas & CO detection control panel
Code 078000
Materials Plastic base with operator console in ABS
Dimensions (LxWxD) 253x327x92mm
IP rating IP44
Operating temperature 0°C to +50°C
Mains input voltage 230Vac 50Hz
System operating voltage 27Vdc
Built-in power supply 27V 1A
Batteries 2x 12V 2.3Ah
Quiescent current Gas detection: 240mA@27Vdc - CO detection: 175mA@27Vdc
Alarm current Gas detection: 275mA@27Vdc - CO detection: 290mA@27Vdc
Auxiliary power consumption Maximum 500mA
Consumption on 230V output Maximum 1A switched via solid state relay
Default settings of the 6 relay outputs (adjustable via software) - 4 relay contacts with double voltage-free changeover contact maximum 230Vac/2A resistive or 80W magnetic valve:
* Relay 1: Alarm level 1
* Relay 2: Alarm level 2
* Relay 3: Alarm level 3
* Relay 4: ON/OFF relay for gas detection - Alarm level 4 for CO detection

- 2 relay contacts with single voltage-free changeover contact 30Vdc/1A:
* Relay 5: Common fault
* Relay 6: Buzzer
Default settings of the 2 transistor outputs (adjustable via software) 1 transistor output 'Common alarm' and 1 transistor output 'Common fault' - maximum 80mA resistive and 50mA inductive
Number of external relay cards Maximum 8
External inputs 1 external input 'Alarm silence' and 1 external input 'System reset'
Programming cable Standard serial cable

Downloads