The MD2400L, analogue addressable fire detection and fire warning system for buildings, has been designed in accordance with European Standards EN54-2:1997/A1:2006 and EN54-4:1997/A1:2002/A2:2006 and is  BOSEC B-9072-FD-954 EN54-13 certified.

The MD2400L fire alarm control panel has a maximum capacity of 3 XP95 detection loops. A maximum of 126 addressable components can be connected on each loop. Communication with the connected detectors and devices is based on the digital XP95 protocol.

The various components of the MD2400 fire alarm control panel are mounted in a synthetic housing with a transparent door. The MD2400L central processing unit includes the main processor card, up to 3 XP95 loop interface cards, the relay card with 10 relays, the system's basic power supply and the Touch screen. The front of the MD2400L fire alarm control panel is equipped with a built-in 7'' colour Touch screen for operating the control panel and for displaying the messages of the system.

The MD2400L fire alarm control panel is equipped as standard with 10 relays, of which 2 monitored outputs, 1 Fail-safe relay for "Common fault", 1 relays for "Fault power supply" and 6 freely programmable relays with potential free change-over contacts.

The MD2400L fire alarm control panel can be connected in a network to other MD2400 or MD2400L fire alarm control panels by means of the optional module "Redundancy Token-ring". Up to 32 MD2400 or MD2400L fire alarm control panels can be connected via the redundant Token-ring. This optional module also allows up to 2 redundant operator consoles to be connected to one MD2400L fire alarm control panel. The capacity of the power supply of the MD2400L fire alarm control panel must be taken into account. The optional module "Redundancy Token-ring" is mounted in a separate housing and must be placed immediately under the housing of the control panel.

The RS485 I/O bus also offers the possibility to connect an MD2400 SIA modem interface and an MD2400 interface ESPA 4.4.4 protocol.

The housing of the MD2400L fire alarm control panel offers space for two batteries with a maximum capacity of 12V 12Ah.

The MD2400L fire alarm control panel is programmed using a PC configuration software.

Technical details

Description MD2400L Fire alarm control panel with redundancy Token-ring
Code 244001RTR
BOSEC EN54-13 certificate B-9072-FD-954
Certificate of Constancy of Performance 1134-CPR-077
Declaration of Performance DoP-MD2400L-2013
Materials & colour housing Self-extinguishing plastic - RAL7035
Dimensions (HxWxD) (665+285)x410x140mm
IP rating IP65
Display and controls Built-in 7'' colour Touch screen
Mains input voltage 230Vac 50Hz
Built-in power supply 27V 1A+0,6A
Batteries - Type Minimum 2x 12V 7Ah - Maximum 2x 12V 12Ah - Genesis
Number of loops 1. 2 or 3 loops - maximum 126 addresses per loop
Relay outputs - 2 monitored circuits (EOL resistor 330Ω + diode per output) - maximum 15 ROSHNI RoLP sounders per output (EN54-13)
- 8 potential free change-over contacts (0,5A/30Vdc) of which 1 Fail-safe for 'Common fault' and 1 for 'Fault power supply'
Maximum load to be connected in quiescent condition (I Max A) 500mA@27Vdc (including the consumption of the control panel, the fire detectors, manual call points, I/O units and other devices)
Maximum load to be connected in alarm condition (I Max B) 1A@27Vdc (including the consumption of the control panel, the fire detectors, manual call points, I/O units, sounders and other devices)
Quiescent current - Basic system current consumption: 236mA (with 1 loop interface card)
- Current consumption per additional loop interface card: 21mA
- Current consumption per additional relay card: 32mA
Alarm current 438mA with 1 loop interface card and with factory setting of the built-in relay card
Maximum load of the auxiliary power supply output 500mA (take into account the maximum load to connect to the control panel in quiescent and in alarm condition)
Standard communication buses of the main processor RABBIT4000 - RS485 I/O bus (operator consoles, repeater panels)
- RS485 loop bus (XP95 detection loops)
- RS485 Token bus (communication between MD2400L & MD2400)
- RS232 bus (communication with PC)
- RS485 EAM bus (communication with graphical software)
Built-in options with requirements according to EN54-2 - Outputs to alarm devices (output type C) (§ 7.8)
- Delays to outputs (§ 7.11)
- Fault signals from points (§ 8.3)
- Disablement of addressable points (§ 9.5)
- Test condition (§ 10.1, § 10.2 and § 10.3)
Other technical data We refer to document HD2400LN05A available for inspection at the manufacturer
Notified body ANPI:1134