XP95 DIN-rail 4-channel I/O unit
The XP95 4-channel I/O unit is an interface equipped with 4 inputs and 4 outputs. This module is available in 2 versions, namely the XP95 4-channel I/O unit for DIN-rail mounting and the XP95 4-channel I/O unit mounted in a plastic housing.
The inputs of the XP95 4-channel I/O unit report the status of up to 4 potential-free NO or NC contacts to a MD2400 or MD2400L fire alarm control panel. Combining NO and NC contacts on one module is not possible.
The 4 inputs of the XP95 4-channel I/O unit are individually addressed. The number of connected contacts can be selected using a jumper setting. The number of connected contacts automatically determines the number of addresses reserved by the XP95 4-channel I/O unit. The address of the first input is set using a DIP-switch. The following inputs are automatically assigned to the chronologically following addresses.
The 4 outputs are provided in the form of an open collector on a 16-pin flat cable connector. Each open collector output can control a 24Vdc relay. The activation of the outputs is independant of the status of the 4 inputs. This module can be used in combination with a relay card with 4 relays.
The XP95 4-channel I/O unit requires a 4-wire cabling, 2 wires for the 24Vdc constant supply voltage and 2 wires for the XP95 detection loop. The cabling between the input of the XP95 4-channel I/O unit and the contact to be supervised is cheched for short circuits and open circuits using EOL resistors.
Technical details
Description | XP95 DIN-rail 4-channel I/O unit |
---|---|
Code | 085325 |
Dimensions (HxWxD) | 102x116x48mm |
Supply voltage | 17 - 28Vdc |
Number of inputs | 4 |
Type of inputs | 4x contact NO or 4x contact NC (voltage-free) |
Number of outputs | 4 |
Type of outputs | Open collector (transistor output) - maximum 50mA resistive |
EOL resistor | 470K |
Alarm resistor | 47K |
Quiescent current | - 4mA on XP95 loop - 13mA@24Vdc |
Alarm current | - 4mA on XP95 loop - 14mA@24Vdc |
Operating temperature | 0°C to +50°C |
Humidity | 0% to 95% (no condensation or icing) |
Terminals | Inputs: screw clamps - Outputs: flat cable |
Supply wiring | Four wire supply: 2x 24Vdc supply voltage and 2x XP95 detection loop |
Cable distance | - maximum 30 meters between XP95 4-channel I/O unit and the contact - shielded cable placed in a separate cable duct |
Number of I/O units per XP95 detection loop | Maximum 7 per loop |
Variant | 085326: XP95 4-channel I/O unit in housing 150x170x80mm IP55 |