|| XTRALIS Aspirating smoke detectors ||
FAAST FLEX – zone aspirating smoke detector – Art. IC-FLX-010
- High-sensitivity aspiration unit equipped with 1 laser detector
- Suitable for 1 sampling pipe with total length of maximum 105 metres
- Quiescent current: 400mA@24Vdc
ON ORDER

|| SECURITON Aspirating smoke detectors ||

ASD-531 - aspirating smoke detector
- Art. SE-ASD-531 -
- Equiped with a highly sensitive smoke detector SSD-31
- 1 detection zone with a maximum surface area of 720m²
- Suitable for 1 sampling pipe with total length of maximum 40 metres
- Quiescent current: 75mA@24Vdc
- Alarm current: 80mA@24Vdc
- To be used in combination with a DFU-911 external dust filter
ON ORDER
ASD-533-1 – aspirating smoke detector
- Art. SE-ASD-533-1 -
- Equipped with a highly sensitive smoke detector SSD-533 and standard display
- 1 detection zone with a maximum surface of 1600m²
- Suitable for 1 sampling pipe with total length of maximum 110 metres
- Quiescent current : 130mA@24Vdc
- Alarm current : 160mA@24Vdc
- To be used in combination with a DFU-911 external dust filter
ON ORDER


ASD-535-1 - aspirating smoke detector
- Art. SE-ASD-535-1 -
- Equipped with standard display
- 1 highly sensitive smoke detector SSD-535-3 not included
- 1 detection zone with a maximum surface of 1600m²
- Suitable for 1 sampling pipe with total length of maximum 110 metres
- Quiescent current: maximum 260mA@24Vdc
- Alarm current : maximum 295mA@24Vdc
- To be used in combination with a DFU-911 external dust filter or with a FBD-25-PC external dust filter for cold stores & freezers
STOCK KEEPING ARTICLE
ASD-535-2 – aspirating smoke detector
- Art. SE-ASD-535-2 -
- Equipped with standard display
- 2 highly sensitive smoke detectors SSD-535-3 not included
- 2 detection zones with a maximum surface of 1600m² per zone
- Suitable for 2 sampling pipes with total length of maximum 110 metres per pipe
- Quiescent current: maximum 290mA@24Vdc
- Alarm current : maximum 350mA@24Vdc
- To be used in combination with a DFU-911 external dust filter or with a FBD-25-PC external dust filter for cold stores & freezers
STOCK KEEPING ARTICLE

|| External dust filters ||

DFU-911 – external dust filter
- Art. SE-DFU-911 -
- For use in standard environments in combination with ASD aspirating smoke detectors
- Dimensions (H x W x D): 210 x 111 x 137 mm
- Tube diameter: 25mm
- Temperature range: 0°C tot +60°C (without condensation)
- Transient humidity: 95% RH (without condensation)
- Continuous humidity: 70% RH (without condensation)
-
STOCK KEEPING ARTICLE